产品中心

Home >产品中心

LEL5(Y30)Residual Current Circuit Breaker

Product DescriptionMachine ParameterSizePDF DownloadCCC证书

1  Application 

LEL5 (electromagnetic) RCCB is mainly suitable for using in circuit up to single phase 230V, three phase 400V, 50 or 60Hz ,  a rated current 16 -100A; enterprises, buildings, hotels and families.  It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line, so it is suitable to avoid the shock hazard and fire caused by earth leakage.

Compliant standard:IEC61008-1.

 

2. Type designation

Sinoart enterprise content manager system | Sinoart CMS

3 Technical data

Specifictions

Rated voltage(v) :

230/400V~

Rated current(A) :

16、25、32、40、50、63、80、100

Rated sensitivity lrn(A)

0.03、0.1、0.3

Residual non-operating current lrno                             

0.5Irn

Poles :

2、4

Model                                 

Rated residual making and breaking capacity lr m

1000A

Max. tripping time

table 1

Mechanical life & Electrical life:

1000  

2000

Pollution

3

Protection 

IP20

Overvoltage

 

Table 1 Max. tripping time (s)

Type   mA Irn 2Irn 5Irn

Non delay

 

0.1

0.06

0.04

Max. tripping time (s)

delay (S)

 

0.5

0.2

0.15

Max. tripping time (s)

 

0.13

0.06

0.04

Tripping time (s)

 

4  Operating conditions.

4.1 : Ambient  temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃

4.2 : Altitude:≤ 2000m;

4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃

4.4 : Mounting type :  Din rail embedded(TH35-7.5)

5. Overall and mounting dimensions (unit:mm) 

Sinoart enterprise content manager system | Sinoart CMS

LEL5(Y30)Residual Current Circuit Breaker