PRODUCTS CATEGORIES
1 Overall
CQC1 (CAC1)series contactors allows you to optimize equipment design and provides reliable and time-saving solution. They are suitable for combination with a thermal relay to compose of a magnetic motor starter.
Features
·High making and breaking capacity
·Electric ratings: AC50/60Hz,690V,up to 95A;
·Remote making& breaking circuits; protect circuit from over-load when assembling with thermal over-load relay;
·Robust construction
·Adjustable number of auxiliary contacts
·Pre-sales support to identify and define customer requirements.
2. Type designation
3 Operating conditions.
When ordering contactors, the following points should be specified:
(a) Product models, such as: CQC1-09;
B) Control voltage Us, such as AC220V;
C) Auxiliary contacts, such as: NO: a pair of normally opened auxiliary contacts, NC: a pair of normally closed auxiliary contacts. ;
D) Quantity of orders, such as 100 sets
If ordering CQC1-09Us: AC220V 100 1ON+1NC
4 Technical data
Note: 3P means three pairs of normal open main contacts. NO: one pair of normal open auxiliary contacts. NC: one pair of normal closed auxiliary contacts.
5 Operating conditions
1 .At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃。
2.Altitude: ≤2000m
3.Pollution degree: 3
4.Overvoltage category: "Ⅱ"
5.Installation position: The installation degree of the tilt and vertical plane should not exceed ±5°.
6. Installation mode: 09-32A is suitable for 35mm Din rail, 40A-95A is suitable for 75mm Din rail.
7.Shock vibration: Products should be installed and used without significant shake, shock and vibration place.
6 Dimensions
No. | Model | Dimensions(mm) | ||
Amax | Bmax | Cmax | ||
1 | CQC1-9、12 | 47 | 76 | 82 |
87 | ||||
2 | CQC1-18 | |||
3 | CQC1-25 | 58 | 86 | 96 |
4 | CQC1-32 | 101 | ||
5 | CQC1-40~63 | 84 | 129 | 116 |
6 | CQC1-80~95 | 96 | 129 | 127 |