产品中心

Home >产品中心

CQB47-63 Miniature Circuit Case Breaker

Product DescriptionMachine ParameterSizePDF DownloadCCC证书

1. Application

·Thermal-magnetic overload protection

·Short circuit protection

·Isolation function

·Single phase and three phase applications(220V/380V)

Suitable for industrial, commercial, high-rise and civil residences circuit protection.

 

2. Type designation

Sinoart enterprise content manager system | Sinoart CMS

3  Technical data

Specifications

Rated voltage(v)

230V/400V(1P)、400V(2P、3P、4P)

Rated current(A)

6、10、16、20、25、32、40、50、63

Poles 

1P、2P、3P、4P

Rated breaking capacity(A)

Table 1

Tripping characteristic

Table 2

Mechanical life

10000

Nominal cross section area (mm2)

Table 3  

Tightening torque (N·m)

2.5

Pollution Degree

Protection class

IP20

Overvoltage category 

 

Table 1:  Rated breaking capacity

Tripping Characteristics Rated current(A) Rated breaking capacity(A) Power factor

B、C 

≤40

6000      

0.65-0.70

B、C

>40

4500

0.75-0.80

D

≤63

4500

0.75-0.80

 

Table 2:  Tripping characteristic  (temperature 30℃)

Model Rated current(A) Initial situation Test current Tripping time Test result Remarks

Delay

≤63

Cold

1.13In

≤1h

Non-tripping     

 

Delay

≤63

Following No.1 test

1.45In

<1h

tripping

Current  smoothly rises to specified value in 5s

Delay

≤32

Cold

2.55In

1<t<60s

tripping

 

Delay

>32

Cold

2.55In

1<t<120s

tripping

 

Instant

Any value

Cold

3、5、10In

≤0.1s

Non-tripping

B、C、D 

Instant

Any value

Cold

5、10、20In

<0.1s

tripping

B、C、D 

 

Table 3:  Normal  cross  section  area: ≤16mm² 

Rated current(A) Nominal cross section area (mm²)

In≤6

1

6≤In≤13

1.5

13<In≤20

2.5

20<In≤25

4

25<In≤32

6

32<In≤50

10

50<In≤63

16

 

Table 4 :  Installation sizes (mm)

Poles a b

1P

66±0.64

72±0.64

2P-4P

69±0.64

75±0.64

 

4  Operating conditions.

4.1 : Ambient  temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃

4.2 : Altitude:≤ 2000m;

4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃

4.4 : Mounting type :  Din rail embedded(TH35-7.5) 

5  Dimensions(unit :mm)

Sinoart enterprise content manager system | Sinoart CMS

CQB47-63 Miniature Circuit Case Breaker