CQB9aL-63 Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)

Product DescriptionMachine ParameterSizePDF DownloadCCC证书

1  Application 

CQB9aL-63 residual current operated circuit breaker is applicable to the circuit with an alternating current of 50Hz or 60Hz, rated-voltage single pole and two lines 230V, three  pole  four lines 400V,  and a rated current up to 63A; when the human body gets an electric shock or the network leak current exceeds the specified value, the residual current operated circuit breaker can rapidly cut off the power supply in trouble within a very short time for the safety of the human body and the powered equipment. With the function of overload and short circuit protection, the residual current operated circuit breaker can be used to protect the circuit or motor from being damaged by overload and short circuit, and can also be used for not-frequent operational transformation in the circuit under normal condition.

Compliant standard: IEC 61009-1 

 

2. Type designation

Sinoart enterprise content manager system | Sinoart CMS

3  Technical data

Specifications 1P+N 3P+N

Rated voltage(v) :

230V~

230~/ 400~

Rated current(A) :

6、10、16、20、25、32、40、50、63

Rated sensitivity lrn (mA)

10、30、100、300

Rated residual non-operating current : lrno(mA)

0.5lrn

Poles :

1P+N

3P+N

Rated breaking capacity : lcu(A)

6000

Rated residual making and breaking capacity lr m

6000

Maximum breaking time of the residual current operating

Table 1

Tripping characteristic :

Table 2

Mechanical life & Electrical life:

Mechanical life:10000 ; Electrical life: 4000

Nominal cross section area S (mm2) :

Table 3

Pollution degree:

2

Protection class:

IP20

Overvoltage category :

Ⅱ、Ⅲ

 

Table 1 Max. breaking time of the residual current operating

Type ln (A) lrn (mA) Breaking time when the residual current assumes the following values (s)

lrn

2lrn

5lrn

General type 

Any value

Any value

0.1

0.05

0.04

 

Table 3  Over current protection characteristics

Rated current(A) Test current Initial status Tripping time Test result Remarks

6~63

1.13In

Cold

t≥1h

Non-tripping

 

6~63

1.45In

Right after test a

t<1h

Tripping

Current  smoothly rises to specified value in 5s

6~63

2.55In

Cold

1s<t<60s(In≤32A)

1s<t<120s(In>32A)

Tripping

6~63

5In

Cold

t≥0.1s

Non-tripping

C

10In

t<0.1s

tripping

 

Table 4 Nominal cross-sectional area 

Nominal cross-sectional area of the copper conductor (mm2)
Rated current (A) Nominal cross-sectional area of the copper conductor (mm2)

6~16

2

20~32

2.5

40~63

4

 

4  Operating conditions.

4.1 : Ambient  temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃

4.2 : Altitude:≤ 2000m;

4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃

4.4 : Mounting type :  Din rail embedded(TH35-7.5)

4.5 Installation conditions
Any direction of the outer magnetic field of the installation site should not exceed 5 times than earth's magnetic field; residual current operated circuit breaker should be mounted vertically, all places inclination no more than 5 °,power position above the handle  , the installation place should be no significant impact and vibration.

5. Overall and mounting dimensions (mm)