PRODUCTS CATEGORIES
Product DescriptionMachine ParameterSizePDF DownloadCCC证书
1 Application
MX shunt tripping device is mainly used for AC 50Hz, rated voltage 230V line and CQB5a series circuit breaker equipped with long distance shunt tripping operation.
Compliant standard: IEC60947-5-1。
2 Technical data
Model | |
Rated voltage of control power supply Us |
AC 230V 50Hz |
Rated insulation voltage (Ui) |
415V |
Operation property |
(70%~110%)Us,the release reliably operates to break the circuit breaker |
Life(operations) |
4000 |
3 Nominal operation conditions.
3.1 Ambient temp. range:-40℃~40℃
3.2 Relative humidity:≤90%/20℃,≤50%/40℃
3.3 Altitude:≤ 2000m
diagram
4 Dimensions (unit:mm)