CQB5aL-63 Residual Current Operated Circuit Breaker with Over-current Protection (Electronic)

Product DescriptionMachine ParameterSizePDF DownloadCCC证书

1  Features

·Overload protection

·Short circuit protection

·Protect people against indirect contacts and additional protection against direct contacts.

·Protect installations against fire hazard due to insulation faults.

·Single phase and three phase applications.

·Control electric circuits

Suitable for industrial, commercial, high-rise and civil residences circuit protection.

Compliant standard: IEC 61009-1 

 

2. Type designation

Sinoart enterprise content manager system | Sinoart CMS

3 Technical data

Specifications

Rated voltage(v) :

230V~/400~

Rated current(A) :

6、10、16、20、25、32、40、50、60、63

Rated sensitivity lrn (mA)

30、50、100

Rated residual non-operating current

0.5 lrn

Poles :

1P+N、2P、3P+N、4P

Rated breaking capacity : lcu(A)

4500

Rated residual making and breaking capacity lr m

2000

Operating time:

Table 1

Tripping characteristic :

Table 2

Mechanical life & Electrical life:

Mechanical life:  6000 ;Electrical life:4500

Nominal cross section area S (mm2) :

Table 3

Pollution degree:

2

Protection class:

IP20

Overvoltage category :

Ⅱ、Ⅲ

 

Table1 Max. Tripping Time

ln (A) lrn (mA) Breaking time when the residual current assumes the following values (s)

lrn

2lrn

5lrn

10lrn

lrtb

6~63

30、100、300

0.1

0.05

0.04

0.04

0.04

a. The test of 5A,10A,20A,50A,100A,200A,500A is only performed for the verification of operation, and is not performed for the magnitude of  current greater than the lower limit of over-current  instant current  tripping range.

b. The test is carried out for the current with the lrn being equal to the lower limit of the over-current instantaneous tripping range for type C or D.

 

Table  2  Over current protection characteristic

Rated current(A) Test current Initial situation Tripping time Test result Remarks

6~63

1.13In

Cold

t≥1h

Non-tripping

 

6~63

1.45In

Right after test a   

t<1h

tripping

Current  smoothly rises to specified value in 5s

6~63

2.55In

Cold

1s<t<60s(In≤32A)

1s<t<120s(In>32A)

tripping

 

6~63

3In

5In

10In

 

16 In

Cold

t≥0.1s

Non-tripping

5In

t<0.1s

tripping

5In

t≥0.1s

Non-tripping

10In

t<0.1s

tripping

10In

t≥0.1s

Non-tripping

20In

t<0.1s

tripping

Note: The terminology “Cold ” means that the test is performed at the base calibration temperature with no load prior to the test.

 

Table 3 Nominal cross-sectional area of the copper conductor

Rated current (A) Nominal cross-sectional area(mm2)

≤10

1.5

10~20

2.5

20~25

4

25~32

6

32~50

10

50~63

16

 

4  Operating conditions.

4.1 : Ambient  temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃

4.2 : Altitude:≤ 2000m;

4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃

4.4 : Mounting type :  Din rail embedded(TH35-7.5)

4.5 Installation conditions
Any direction of the outer magnetic field of the installation site should not exceed 5 times than earth's magnetic field; residual current operated circuit breaker should be mounted vertically, all places inclination no more than 5 °,power position above the handle  , the installation place should be no significant impact and vibration. 

5.Dimensions and installation sizes (mm) 