PRODUCTS CATEGORIES
1 Features
·Overload protection
·Short circuit protection
·Protect people against indirect contacts and additional protection against direct contacts.
·Protect installations against fire hazard due to insulation faults.
·Single phase and three phase applications.
·Control electric circuits
Suitable for industrial, commercial, high-rise and civil residences circuit protection.
Compliant standard: IEC 61009-1
2. Type designation
3 Technical data
Specifications | |
Rated voltage(v) : |
230V~/400~ |
Rated current(A) : |
6、10、16、20、25、32、40、50、60、63 |
Rated sensitivity lrn (mA) |
30、50、100 |
Rated residual non-operating current |
0.5 lrn |
Poles : |
1P+N、2P、3P+N、4P |
Rated breaking capacity : lcu(A) |
4500 |
Rated residual making and breaking capacity lr m |
2000 |
Operating time: |
Table 1 |
Tripping characteristic : |
Table 2 |
Mechanical life & Electrical life: |
Mechanical life: 6000 ;Electrical life:4500 |
Nominal cross section area S (mm2) : |
Table 3 |
Pollution degree: |
2 |
Protection class: |
IP20 |
Overvoltage category : |
Ⅱ、Ⅲ |
Table1 Max. Tripping Time
ln (A) | lrn (mA) | Breaking time when the residual current assumes the following values (s) | ||||
lrn |
2lrn |
5lrn |
10lrn |
lrtb |
||
6~63 |
30、100、300 |
0.1 |
0.05 |
0.04 |
0.04 |
0.04 |
a. The test of 5A,10A,20A,50A,100A,200A,500A is only performed for the verification of operation, and is not performed for the magnitude of current greater than the lower limit of over-current instant current tripping range.
b. The test is carried out for the current with the lrn being equal to the lower limit of the over-current instantaneous tripping range for type C or D.
Table 2 Over current protection characteristic
Rated current(A) | Test current | Initial situation | Tripping time | Test result | Remarks |
6~63 |
1.13In |
Cold |
t≥1h |
Non-tripping |
|
6~63 |
1.45In |
Right after test a |
t<1h |
tripping |
Current smoothly rises to specified value in 5s |
6~63 |
2.55In |
Cold |
1s<t<60s(In≤32A)
1s<t<120s(In>32A) |
tripping |
|
6~63 |
3In
5In
10In
16 In |
Cold |
t≥0.1s |
Non-tripping |
B |
5In |
t<0.1s |
tripping |
|||
5In |
t≥0.1s |
Non-tripping |
C |
||
10In |
t<0.1s |
tripping |
|||
10In |
t≥0.1s |
Non-tripping |
D |
||
20In |
t<0.1s |
tripping |
Note: The terminology “Cold ” means that the test is performed at the base calibration temperature with no load prior to the test.
Table 3 Nominal cross-sectional area of the copper conductor
Rated current (A) | Nominal cross-sectional area(mm2) | |
≤10 |
1.5 |
|
10~20 |
2.5 |
|
20~25 |
4 |
|
25~32 |
6 |
|
32~50 |
10 |
|
50~63 |
16 |
4 Operating conditions.
4.1 : Ambient temp. range:-5℃~+40 ℃,average temperature in 24 hours not exceed +35℃
4.2 : Altitude:≤ 2000m;
4.3 : At mounting site, relative humidity not exceed 50% at the max temperature of +40 ℃,higher relative humidity is allowable under lower temperature, for example ,RH could be 90% at +20 ℃
4.4 : Mounting type : Din rail embedded(TH35-7.5)
4.5 Installation conditions
Any direction of the outer magnetic field of the installation site should not exceed 5 times than earth's magnetic field; residual current operated circuit breaker should be mounted vertically, all places inclination no more than 5 °,power position above the handle , the installation place should be no significant impact and vibration.
5.Dimensions and installation sizes (mm)